Products

Our Products

Combined Instrument Transformers (CTVT) :

The combined instrument transformer (CTVT) offers the station designer the ability of being able to accommodate the current transformer and the voltage transformer in one free-standing unit. This allows optimum use of substation space while yielding cost savings by elimination of one set of mounting pads and support structures. In addition, installation time is greatly reduced.

Features :

Meets all latest IEC and IS metering and protection classes, including special core classes (other standards available on request)

Low weight & minimum oil volume design

Available in both single phase and three phase design

High accuracy up to 0.1 and 0.2s class

Rated primary currents up to 3000 A

Rated secondary current 1 A or 5 A

Rated short circuit withstand up to 40 kA for 3 secs

Highly refined and processed oil/paper insulation system

True hermetical sealing

Uniformly distributed secondary windings guarantee accurate transformation at both rated and high currents

Stable accuracy over a long period of time

Successful field experience since the manufacture of the first CTVT in 2001

CTs are virtually maintenance free during a long lifetime

Only one foundation required in the switchyard as a consequence of combining the voltage and current sensing functions in one transformer

Particulars Unit General Specifications
Highest System Voltage KV

12

36

Applicable Standard IS 2705, IS 3156, IS 16227 & IEC 61689
Rated System Voltage KV

11

33

One Minute Power Frequency Dry Withstand Voltage on Primary Winding KV

28

70

One Minute Power Frequency Withstand Voltage On Secondary Windings KV 3 KV
Lightning Impulse KVp

95

170

Rated Primary Current A As per requirement
Rated Secondary Current A 5A or 1A
Short Time Thermal Withstand Current/Duration KA sec As per requirement
Number of Cores As per requirement
CT Output / Accuracy As per requirement
Rated Primary Voltage KV

11kV

33kV

Rated Secondary Voltage V 110V/√3 or 110V/3 or 110V.
Voltage Factor 1.2cont. 1/9 for 30 sec
Number of Secondary windings Max 3
PT Output/Accuracy As per requirement

*Above specifications are for indicative purposes only. CTPTs upto 36 KV can be manufactured in any specific requirement of the customer.