Meets all latest IEC and IS metering and protection classes, including special core classes (other standards available on request)
Low weight & minimum oil volume design
High accuracy up to 0.1 and 0.2s class
Rated primary currents up to 3000 A
Rated secondary current 1 A or 5 A
True hermetical sealing
Rated short circuit withstand up to 40 kA for 3 secs
Highly refined and processed oil/paper insulation system
Available in both dead tank & live tank design
True hermetical sealing
Uniformly distributed secondary windings guarantee accurate transformation at both rated and high currents
Stable accuracy over a long period of time
Successful field experience since the manufacture of the first current instrument transformer in 2001
CTs are virtually maintenance free during a long lifetime
| Particulars | Unit | General Specifications |
|---|---|---|
| Highest system voltage | KV | 12 36 145 |
| Applicable Standard | IS 2705, IS 16227 & IEC 61689 | |
| Rated System Voltage | KV | 11 33 132 |
| One Minute Power Frequency Dry With stand Voltage on Primary Winding | KV | 28 70 275 |
| One Minute Power Frequency Withstand Voltage On Secondary Windings | KV | 3 KV |
| Lightning Impulse | KVp | 95 170 650 |
| Rated Primary Current | A | As per requirement |
| Rated Secondary Current | A | 5A or 1A |
| Short Time Thermal Withstand Current/Duration | KA/s | As per requirement |
| Number of Cores | As per requirement | |
| Output/Accuracy | As per requirement | |
*Above specifications are for indicative purposes only. CTs upto 145 KV can be manufactured in any specific requirement of the customer.
*CTs can also be manufactured in rein cast insulation (indoor & outdoor).